4 hours ago Lynnie asked ... BT Studio 4500 cordless telephone?    |    David Dawes asked ... How to recoil the starter spring - Champion R484TR?    |    peter high asked ... How can I set time on my Neff oven?    |    Michael asked ... Mountfield empress drive belt?    |    John Barton asked ... How do i clear the TAM?    |    Click here to ask your question

Solenoid vale not opening?

Trianco/Monoflame Minor/Danfoss pump(new)
Pump changed due to fault, now the solenoid valve remains closed not allowing fuel to flow ! Lock-out does not "lock-out" but ignitor and fan work OK. HELP !!!
Mark Golledge, December 2007
Hi Mark
Have the solenoid valve coil checked and prove there is a signal getting to it from the control box. Also check that the pump has been vented and fully primed. Has the operating oil pressure been set correctly on the new pump.

D.R., January 2008
link Click here to see other fixes for Danfoss.