Carol asked ... How to remove roller from lawnmower?    |    Ariana Orellana asked ... Code?    |    Lynnie asked ... BT Studio 4500 cordless telephone?    |    David Dawes asked ... How to recoil the starter spring - Champion R484TR?    |    peter high asked ... How can I set time on my Neff oven?    |    Click here to ask your question

the bar pressure is 0 where is the valve located to pressurise the system?

no pressure in system i put stop leak into two rads.always having to bleed upstairs rads which are half empty and noisey.im looking to fill system with more water to get pressure back in pressure valve which is 0 at moment .i have a potterton prima f is the tap in boiler or outside it?
jimmy, April 2011
A Prima F boiler (generally speaking), will be fitted to an open vented system so doesn't have a filling point, it fills via the F&E cistern (probably in the loft).

It's possible that the ball valve on the system is stuck closed or the cold feed that fills the system is blocked.

However, if the system has been modified and fitted to a pressurised set up and you have a guage reading 0, the filling point should be located close to the guage, there would also be an expansion vessel nearby too.

Carefree, April 2011
link Click here to see other fixes for Potterton Prima F.