David Dawes asked ... How to recoil the starter spring - Champion R484TR?    |    peter high asked ... How can I set time on my Neff oven?    |    Michael asked ... Mountfield empress drive belt?    |    John Barton asked ... How do i clear the TAM?    |    John asked ... How can I mend my binatone veva 1210 handset?    |    Click here to ask your question

Worcester Greenstar 40CDi fan running contiously?

I have a Worcester Greenstar 40 CDi boiler which had displayed an EA fault. I rest this but all the boiler does now is run the fan continuously and nothing else.
Rick, August 2017
Sadly, it's time to replace the circuit board. I replaced one for a customer. Then, my own of exactly the same age failed in the same way on Boxing Day. Makes you wonder if there is a clock built in !

Gasheat55, September 2017
EA = flame failure

You would have to test each component involved in IGNITION SEQUENCE

Gas supply
Gas valve
Fan
Spark generator
Ignition & detection electrodes
Air gas mixture
Pcb
Flue
& finally the CONDENSATE TRAP

You will need
Multimeter
Manometer
Flue gas analyser
& test procedures which can be acquired by ringing Worcester tech

Asbestos, August 2017