Michael asked ... Mountfield empress drive belt?    |    John Barton asked ... How do i clear the TAM?    |    John asked ... How can I mend my binatone veva 1210 handset?    |    Kurt asked ... How can i mend my Aiwa HV-FX7700K?    |    Laetitia asked ... Toyota overlocker model 3400 D?    |    Click here to ask your question

how to fix my glowworm boiler f6 fault code?

I have a glow worm 18hxi boiler with fault f6 thermistor can I replace these
Samuel, April 2018
Yes you can, but do you need to?

The Glow Worm help page says this for F6:

*The Heating Flow NTC Thermistor Has Gone Open Circuit (Should Read 12Kohms at 20C)
*Wiring Harness Fault Or Connection Fault Between The Heating Flow Thermistor And The Main PCB
*Flow & Return Piped Up The Wrong Way Round (Hxi Model Only)
*External System Pump Circulating The Wrong Way Around The System (Hxi Model Only)

So: check the connections, check the thermistor and only replace if it has failed.

Do, however, consider getting someone competent to look at it.

Ghiutdf, April 2018