Lynnie asked ... BT Studio 4500 cordless telephone?    |    David Dawes asked ... How to recoil the starter spring - Champion R484TR?    |    peter high asked ... How can I set time on my Neff oven?    |    Michael asked ... Mountfield empress drive belt?    |    John Barton asked ... How do i clear the TAM?    |    Click here to ask your question

My 9.5kw Gainsborough shower trips the fuse after a few minutes?

Ive had my 9.5kw Gainsborough shower for over a year now. At first, every few months it would trip the fuse.Now it does it every time after about 3-5 minutes. What could be the problem and how do I fix it? Im curious as to why it has developed over the months? Could it be the shower?
Any help would be great.
James, September 2007
Hi,

With a 9.5 kW shower, you need at least a 40 amp fuse. If you have a 30 amp fuse, as is normal for some lower rated showers, it will trip. It may be the case that you got a new more powerful shower but didn't upgrade the fuse...?

The Dar, October 2007
9.5 kw what model

hi-spec plumbing, September 2007