Dave asked ... Repair kettle lid?    |    Sandy asked ... Replace vertical gear on Singer Fashion Mate 252?    |    Blaablaa asked ... How can I fix?    |    pete asked ... Flymo 330 turboglide?    |    keith asked ... Fuseboard( s) location of renault trafic t1100 1993?    |    Click here to ask your question

What is wrong with my Ferroli Modena 102?

I'm having a pilot flame problem with my boiler. For the last month I have noticed that the pilot light and flame does not come on when I switch on the hot water tap or the central heating. However, after switching on the hot water tap or the central heating, if I hit the boiler on the side this seems to cause the pilot light and flame to ignite. Also, i've noticed that if the central heating is on and I switch the hot water tap on and then off, then the flame goes off even though the the central heating is still on. Then, I have to hit the boiler again to re-ignite it. I have already changed circuit board, thermostat and water pressure switch but still get the same problem. Any ideas??

I am having to tap my boiler to make the pilot light come on so that I can get hot water or for the central heating to work. I have changed the circuit board, the thermostat and the water pressure switch but this has not changed anything. What do you recomend I do?
James Lee, January 2008
Hi James, it is possible that pilot injector is partialy blocked and requires to be cleaned or replaced. I would suggest you have this fault checked by a registered engineer.

D.R., January 2008
have you checked the spark igniter i had a similar problem with my boilerand the igniter had bent and was touching the gas burner

malcolm, January 2008