Don asked ... Find the charger or how to convert the battery?    |    Tanzania asked ... How can i mend my sanyo fwbp505f q?    |    Mark Goodwin asked ... Mount field 725m ride on mower?    |    Joan Sorrentino asked ... Barcalounger issue?    |    David asked ... Not starting until I bang door closed?    |    Click here to ask your question

Ferroli Boiler - Modena 80E (G.C. No. 47-267-05?

My Ferroli boiler is leaking from the overflow.
I have had a new PRV and had it descaled but it is still
leaking. The central heating pressure gauge is high at 3.
What could be the reason?
Jo, February 2008
Hi Jo

It is caused by either

1. Filling loop left on or not shutting off properly.

2. A perforated heat exchanger causing mains cold water to enter the central heating.

3. Expansion vessel in boiler needs recharging or needs replacing.

Hope this helps

Mark Corgi Engineer

Mark, March 2008
I think that the pressure is too high try reducing it to 2 bar

Brian r, February 2008
link Click here to see other fixes for Ferroli Modena 80E.