Don asked ... Find the charger or how to convert the battery?    |    Tanzania asked ... How can i mend my sanyo fwbp505f q?    |    Mark Goodwin asked ... Mount field 725m ride on mower?    |    Joan Sorrentino asked ... Barcalounger issue?    |    David asked ... Not starting until I bang door closed?    |    Click here to ask your question

Ferroli 80E?

The boiler is building up the pressure to 3 after reducing it to 1.5 - new PRV value still do not stop the overflow.
JO, February 2008
check your filling loop is closed. it's a silver flexi pipe coming from the cold, going to the central heating return, thus filling the system with pressure.

r. parfitt, February 2008