Sandy asked ... Replace vertical gear on Singer Fashion Mate 252?    |    Blaablaa asked ... How can I fix?    |    pete asked ... Flymo 330 turboglide?    |    keith asked ... Fuseboard( s) location of renault trafic t1100 1993?    |    Janet asked ... Neff B1641 door not closing at top?    |    Click here to ask your question

How to Adjust the pressure after bleeding a radiator?

I'm decorating and need to remove a radiator. When i put it back i will have to re pressurise the system but the manual does not show how to do this. I know it will just be one of the taps but which one?
Baxi 105e
Sean Patterson, March 2008
Baxi 105 will have a 'filling loop' under the boiler. It connects the mains water to enter the central heating water.

Open the valves on each side of this loop and you will hear the water entering. WATCH the pressure rise on the meter under the flap at the boiler bottom!! Raise this pressure to 1 - 1.5 Bar, & close the valves. It may need more than one go to replace a radiator.

Steve, March 2008