Don asked ... Find the charger or how to convert the battery?    |    Tanzania asked ... How can i mend my sanyo fwbp505f q?    |    Mark Goodwin asked ... Mount field 725m ride on mower?    |    Joan Sorrentino asked ... Barcalounger issue?    |    David asked ... Not starting until I bang door closed?    |    Click here to ask your question

Vaillant Ecotech 837 plus lossing pressure over 3 weeks?

I have noticed when central heating is off boiler pressure drops from 80% to 25% in 2 days. when ch is on takes 3-weeks.
How can I know if there is any leaks as visible pipe work and radiators look ok.
Patel, March 2008
Not 100% sure but if no leaks on system then probably an internal leak in your Domestic Hot Water (secondary) heat exchanger. Allowing central heating pressure to pass into DHW system.
Solution - Replace secondary heat exchanger. Old black "plastic" exchangers are known for this and are obsolete. Replace with new metal exchanger.

Colcreate, April 2008