3 hours ago Sandy asked ... Replace vertical gear on Singer Fashion Mate 252?    |    Blaablaa asked ... How can I fix?    |    pete asked ... Flymo 330 turboglide?    |    keith asked ... Fuseboard( s) location of renault trafic t1100 1993?    |    Janet asked ... Neff B1641 door not closing at top?    |    Click here to ask your question

service riello 40 boiler?

HI,
My riello 40 boiler is firing up but not starting. I have already bleed it and still cant get it to work. I wanted to try to service it to see if anything was broken, not sure how to do this. Any ideas?
Jules, March 2008
I had this problem John and I cleaned the Photo Cell on the box and it seems to have cured it.

Dónal, March 2008
Directly it sounds that your burner isn't actually pumping any oil - the oil pump has an electrically operated solenoid valve (usually a 3 wire connection) built into it that only opens after about 8 seconds of the burner trying to start - this is called the purge time. If oil is being sprayed you should see a wet area on the wall directly in front of the nozzle. I assume that your electrodes are sparking of course!

John, March 2008