John Barton asked ... How do i clear the TAM?    |    John asked ... How can I mend my binatone veva 1210 handset?    |    Kurt asked ... How can i mend my Aiwa HV-FX7700K?    |    Laetitia asked ... Toyota overlocker model 3400 D?    |    Jo-Anne O'Mullane asked ... Clear E1 error code on smeg dishwasher with no water or leak?    |    Click here to ask your question

boiler losing water pressure?

combi boiler losing water pressure water drips out vent pipe
make is a jaguar model is a 28ktvs can anyone help

keith wells
keith wells, March 2008
sounds like your SAFETY DISCHARGE VALVE needs to replace on your boiler

TJ, April 2008
if the pressure exceeds 3bar then a pressure relief valve opens to discharge the excess,once the excess is discharged the valve should close and the water stop coming out.Sometimes the valve doesnt close properly and you have to top up the boiler frequently.If the water stop valve on the filling loop doesnt close fully and you leave the braided hose connected then the boiler will continually fill and the pressure will rise and start to discharge at 3bar.So check the pressure gauge/display to determine whats happening.

combiking, March 2008