Blaablaa asked ... How can I fix?    |    pete asked ... Flymo 330 turboglide?    |    keith asked ... Fuseboard( s) location of renault trafic t1100 1993?    |    Janet asked ... Neff B1641 door not closing at top?    |    Steve asked ... Gilera runner 180 vxr 2001 ignition replacement?    |    Click here to ask your question

How can i stop getting air in my heating system?

I have to bleed my radiators about twice a week. My system is a standard y plan. I have recently replaced the motorised valve with a honeywell model due to a leaking danfoss type. how can i get rid of the air permanantly?
graham Johnson, March 2008
Are you 100% certain it is air, not hydrogen that you are continually venting?

Hydrogen is given off due to reaction between you systems metal components and corrosive water.......
If you are venting, you also must be adding top up water too then, worsening the problem.

Has your system water been properly treated, you may need to get your system flushed, nutarlized and treated to solve this problem.

T, March 2008