Blaablaa asked ... How can I fix?    |    pete asked ... Flymo 330 turboglide?    |    keith asked ... Fuseboard( s) location of renault trafic t1100 1993?    |    Janet asked ... Neff B1641 door not closing at top?    |    Steve asked ... Gilera runner 180 vxr 2001 ignition replacement?    |    Click here to ask your question

baxi 105HE combi is short cycling?

my Baxi 105HE combi boiler works ok for hot water but in heating it runs for 5 seconds and off for 15 seconds constantly. temperature indicator only gets up to 50 C. Pump is working. Return water is only warm.Is it a circulation problem or is the stat faulty. How do you check
jon mosley, April 2008
it is likely your central heating temp sensor (thermistor) needs replacing. costs about 10 quid and takes 5 minutes to change

brian, October 2008