8 mins ago Don asked ... Find the charger or how to convert the battery?    |    Tanzania asked ... How can i mend my sanyo fwbp505f q?    |    Mark Goodwin asked ... Mount field 725m ride on mower?    |    Joan Sorrentino asked ... Barcalounger issue?    |    David asked ... Not starting until I bang door closed?    |    Click here to ask your question

baxi 105HE combi is short cycling?

my Baxi 105HE combi boiler works ok for hot water but in heating it runs for 5 seconds and off for 15 seconds constantly. temperature indicator only gets up to 50 C. Pump is working. Return water is only warm.Is it a circulation problem or is the stat faulty. How do you check
jon mosley, April 2008
it is likely your central heating temp sensor (thermistor) needs replacing. costs about 10 quid and takes 5 minutes to change

brian, October 2008