Sandy asked ... Replace vertical gear on Singer Fashion Mate 252?    |    Blaablaa asked ... How can I fix?    |    pete asked ... Flymo 330 turboglide?    |    keith asked ... Fuseboard( s) location of renault trafic t1100 1993?    |    Janet asked ... Neff B1641 door not closing at top?    |    Click here to ask your question

how do you drop system/boiler pressure on a Baxi 105e combi boiler?

I need to check the pressue in the expansion tank, and re-pressurise it if needed. When the central heating is switched on after about 10 mins the boiler pressure goes over 3 bar.
pete, April 2008
turn off boiler (at 3amp spur) turn both flow and return pipe isolating valves (beneath the boiler) to the off position.
Drain all water from the boiler via the drain cock (behind the pump) then test and recharge your expansion vessel as required.

When refilling the boiler, make sure to bleed the pump and ony run the pump (keep switching the boiler off before it fires) until the sloshing water noise abaits (ie all the air os out of the boiler) before firing

remeber to top up your system water back to 1-1.5 bar after you refill the boiler and bleed of the uppermost rads in the house.

T, April 2008