Tom asked ... Service manual for Lawnflite 908LA?    |    John asked ... Scantronics 9450 box stuck shut?    |    Pekaye asked ... Clutch Cable change?    |    Richard asked ... Mountfield SP414 mower, revs too high?    |    Don asked ... Find the charger or how to convert the battery?    |    Click here to ask your question

Pressure in Worcester 35di boiler?

The pressure for my boiler drops very quickly. after filling the pressure to about 1.5 it drops to to zero in about 6 hours. do i need to replace the pressure relief valve?
prav, May 2008
Whatever is causing water to be lost from the system is the problem, not necessarily the PRV.
Check the expansion vessel has not lost its gas charge, or has its diaphragm perforated. It should take several seconds with the filling tap open to recharge the system to 1.5bar (maybe about 10s). If it "recharges" very quickly this is an indication of expansion vessel failure, as is a large change in system pressure from cold to hot. If it goes over 3 bar the PRV is designed to "drip".
Look for underfloor leaks too.

Phil J, May 2008