Don asked ... Find the charger or how to convert the battery?    |    Tanzania asked ... How can i mend my sanyo fwbp505f q?    |    Mark Goodwin asked ... Mount field 725m ride on mower?    |    Joan Sorrentino asked ... Barcalounger issue?    |    David asked ... Not starting until I bang door closed?    |    Click here to ask your question

How can i fix my Potterton Puma 80 combination boiler?

When I turn on the hot water tap at the sink, the boiler fires up but shuts off after 5 seconds. It does the same from cold or when central heating is on. System pressure is at about 2 Bar.
Hot water Pressure and flow at sink when tap opened is a bit low. Mains pressure on cold side is good. any ideas?
Peter Butler, May 2008
either the inline filter on the water main into the boiler is blocked (should be cleaned every service interval), you dhw thermister has gone faulty, or the plate to plate heatexchanger has become partially blocked and may need replacing........try the filter first...a common problem