Don asked ... Find the charger or how to convert the battery?    |    Tanzania asked ... How can i mend my sanyo fwbp505f q?    |    Mark Goodwin asked ... Mount field 725m ride on mower?    |    Joan Sorrentino asked ... Barcalounger issue?    |    David asked ... Not starting until I bang door closed?    |    Click here to ask your question

my halstead best 50 keeps loosing pressure?

My halstead best 50 keeps loosing pressure. I top up the system but the pressure goes within 30 minutes. The overflow pipe outside keeps dripping. I have checked the radiators/pipework for leaks but cant find any.
Paul Hagan, June 2008
because its going out the overflow (pressure relief valve)outside as you said,????

your 3 bar safety valve has opened up either due to yourself over pressurising the boiler or due to a fault like below. now the valve isnt shut 100% due to dirt or similar and is allowing system water out.

boiler cold--guage around 1-1.5bar
boiler with heating on for 15 mins--guage around 2-2.5bar
(normal operation)

if cold is correct then with heating on pressure guage rises to 3+bar then expansion vessel needs recharged or replaced.

just mentioned cos 2 sometimes related.

iain, June 2008