Sandy asked ... Replace vertical gear on Singer Fashion Mate 252?    |    Blaablaa asked ... How can I fix?    |    pete asked ... Flymo 330 turboglide?    |    keith asked ... Fuseboard( s) location of renault trafic t1100 1993?    |    Janet asked ... Neff B1641 door not closing at top?    |    Click here to ask your question

How do I fix pressure to allow hot water to work?

I currently have no hot water - I think the pressure has dropped very low (to the 1 on guage) when it should be at 3 and the water tank needs filling up. How would I go about finding how/where to do this please
I have a 24i RSF Worcester Combi Boiler - Thanks
Emily, July 2008
if the boiler lights when you turn heating on and does not when you open tap then flow turbine more than likely the fault.

give us a little more detail on what does work if you wish to hear a more definate answer

iain, July 2008
Your boiler should:

1: be on 1 - 1.5 cold on pressure guage
2: should not be on 3.
3: when heating on should rise from cold 1 - 1.5 up to 2 - 2.5
(as the hot water expands) and cool again to 1 - 1.5.

is your heating working?

iain, July 2008