Don asked ... Find the charger or how to convert the battery?    |    Tanzania asked ... How can i mend my sanyo fwbp505f q?    |    Mark Goodwin asked ... Mount field 725m ride on mower?    |    Joan Sorrentino asked ... Barcalounger issue?    |    David asked ... Not starting until I bang door closed?    |    Click here to ask your question

FERROLI PROBS?

not sure if am in the rite place here... hv a question for the plumbers... i also have a nuisance ferroli... pressure reading at 3 bit despite bleeding loads of water from radiator it refills itself... overflow constantly dripping water... where abouts can i attach a bike pump to? (no rude replies plz!) is there any danger in doing this? hv kids to think about... if i cant fix this myself plz can u advise me of what would be a reasonable price to fix this problem... yr response would be much appreciated!
MINXY, August 2008
hi check filling loop is off disconnect if pos reduce pressure in system to 1 bar check relief valve is holding if not replace it

terryb, August 2008
check the filling loop silver coloured hose under boiler is not open..or passing disconnect it from the connection then remove water from system..i susprdect your filling loop is open ..if this does not cure repost and i will advise

corgi bloke, August 2008