Don asked ... Find the charger or how to convert the battery?    |    Tanzania asked ... How can i mend my sanyo fwbp505f q?    |    Mark Goodwin asked ... Mount field 725m ride on mower?    |    Joan Sorrentino asked ... Barcalounger issue?    |    David asked ... Not starting until I bang door closed?    |    Click here to ask your question

baxi 105e too much pressure?

my boiler baxi 105e sits at 1.5 bar no problem but when asked for ch pressure goes up and it blows off at 2.5bar whats causing this
pawbroon, September 2008
most common problem, expansion vessel flat or dead. 95% chance its dead.

options are to recharge it if its ok but flat or
1: replace like for like vessel in boiler
2: fit remote vessel to ch system somewhere hidden.

iain, September 2008