David Dawes asked ... How to recoil the starter spring - Champion R484TR?    |    peter high asked ... How can I set time on my Neff oven?    |    Michael asked ... Mountfield empress drive belt?    |    John Barton asked ... How do i clear the TAM?    |    John asked ... How can I mend my binatone veva 1210 handset?    |    Click here to ask your question

How can i fix my Halstead ace high boiler?

when i call for hot water only , the central heating is coming on and i only get minimum hot water at a slow rate.
denisejohnson1@homecall.co.uk, September 2008
all i know is if you want the parts the best place to go is adlink ( www.adlinkuk.com )

PAUL DICKENS, September 2008
sounds like divertor valve not shutting off ch supply when demanding hw.

basically valve should close ch supply to allow heated system water to heat your domestic water. if its not working properly you'll be able to feel all the heat going down ch pipe to rads and water will be luke warm at tap.

iain, September 2008