Karen asked ... Royal 480nt cash register?    |    andrew smith asked ... 2009 fiesta 1388 cc titainum?    |    Eric asked ... Strimmer fuel line?    |    Frank asked ... Working fine. No cold air?    |    c.m.brown asked ... Replace chuck on aeg power drill sb2e 700r?    |    Click here to ask your question

glow worm swift flow 100?

the central heating comes on even when the timer is on off. The timer is a siemans rwb7 which was recently fitted replacing rwb100 thinking it was a faulty timer. The timer switches the heating on but boiler keeps working switching on an off even after the timer has gone past the off trip.
mike juhasz, October 2008
Not certain think the switching is should be volt free
check that room stat cable is not close to a mains supply as current induced can affect a volt free supply

a, October 2008