Lynnie asked ... BT Studio 4500 cordless telephone?    |    David Dawes asked ... How to recoil the starter spring - Champion R484TR?    |    peter high asked ... How can I set time on my Neff oven?    |    Michael asked ... Mountfield empress drive belt?    |    John Barton asked ... How do i clear the TAM?    |    Click here to ask your question

s30 heatline pressure keeps going above 3 bar ?

the combi heatline s30 pressure in boiler keeps going up above the limt even though the loop filler is not switched on can anyone suggest possible cause
frnky500, November 2008
disconnect filling loop and wait if it still goes up its the plate to plate thats gone.

gasbanni, December 2008
i could be the expansion vessel. it need to be
repressurised or replaced

b, November 2008