HT asked ... Radio code Philips 22RC200/35?    |    Roberta asked ... DW5080?    |    Dave asked ... Toilet Push Button not flushing properly?    |    Dave asked ... Repair kettle lid?    |    Sandy asked ... Replace vertical gear on Singer Fashion Mate 252?    |    Click here to ask your question

What is Wrong?

Vokera Excell Boiler
When the system is turned on the water pressure
increases to 3Bar and PRV releases water outside
The system is working ok as all the radiators get
warm, but I haveto keep topping up the pressure.
Does the expansion vessel need Pressurising?
Russ, December 2008
Yes, sounds like the expansion vessel needs recharging, explanations here and elsewhere (key points It takes more pumping than you expect, and you need zero pressure in the system while pumping, stop at 11 psi or so). Do it soon before the PRV needs replacing (left unfixed the PRV will develop a permanent drip).

c, December 2008
link Click here to see other fixes for Vokera.