1 hour ago Sandy asked ... Replace vertical gear on Singer Fashion Mate 252?    |    Blaablaa asked ... How can I fix?    |    pete asked ... Flymo 330 turboglide?    |    keith asked ... Fuseboard( s) location of renault trafic t1100 1993?    |    Janet asked ... Neff B1641 door not closing at top?    |    Click here to ask your question

Ideal Classic Boiler/Drayton Tempus seven programmer?

This morning the heating failed to come on. Initially I thought the boiler was the problem, yet the pilot light is still on.
The Drayton Tempus seven still has its two lights on, but is unable to fire up the system.

My question is, is it likely that its the programmer at fault and not the boiler and by simply replacing the Tempus seven, will solve the problem ?

Thanks
Richard
Richard Addis, December 2008
I had the same problem with a Tempus 3.
I thought it was the zone valve that had gone wrong.
It turned out that the programmer was showing the heating to be on but it wasn't telling the valve (no live feed to valve).

JohnK, January 2009
do the motorised valves move when heating is called for

b, December 2008