Don asked ... Find the charger or how to convert the battery?    |    Tanzania asked ... How can i mend my sanyo fwbp505f q?    |    Mark Goodwin asked ... Mount field 725m ride on mower?    |    Joan Sorrentino asked ... Barcalounger issue?    |    David asked ... Not starting until I bang door closed?    |    Click here to ask your question

what should i do?

i have a worcester 24i RSLF combi boiler and its reading that there is no bar pressure at all.
steph, January 2009
The boiler needs refilling.Look under the boiler and you should see a filling loop.Connect this to the pipe and switch the water valve on watching the gauge as it fills.Let it get to 1 bar,then turn off the water valve and disconnect the pipe.Do not let it get to 3 bar as the boiler has a safety valve which will blow off if you go above that level.

Tony S, January 2009