Don asked ... Find the charger or how to convert the battery?    |    Tanzania asked ... How can i mend my sanyo fwbp505f q?    |    Mark Goodwin asked ... Mount field 725m ride on mower?    |    Joan Sorrentino asked ... Barcalounger issue?    |    David asked ... Not starting until I bang door closed?    |    Click here to ask your question

chaffoteaux et maury se combi?

my pressure keeps rising until boiler knocks off,then when presssure drops comes back on.could i have accidentally over filled it
greg robinson, January 2009
No this is problem is happening because the expansion vessel with in the boiler is flat or the diaphragm is burst. To test remove the shredder cap from the expansion vessel located at the back of the boiler, push on the pin. If water comes out then the diaphragm within the vessel is burst (new expansion vessel required) if nothing comes out then the vessel is flat (use a bicycle pump with a guage and pressureise to 1bar.)

Simon, March 2009