4 hours ago Sandy asked ... Replace vertical gear on Singer Fashion Mate 252?    |    Blaablaa asked ... How can I fix?    |    pete asked ... Flymo 330 turboglide?    |    keith asked ... Fuseboard( s) location of renault trafic t1100 1993?    |    Janet asked ... Neff B1641 door not closing at top?    |    Click here to ask your question

chaffoteaux et maury se combi?

my pressure keeps rising until boiler knocks off,then when presssure drops comes back on.could i have accidentally over filled it
greg robinson, January 2009
No this is problem is happening because the expansion vessel with in the boiler is flat or the diaphragm is burst. To test remove the shredder cap from the expansion vessel located at the back of the boiler, push on the pin. If water comes out then the diaphragm within the vessel is burst (new expansion vessel required) if nothing comes out then the vessel is flat (use a bicycle pump with a guage and pressureise to 1bar.)

Simon, March 2009