2 hours ago Pekaye asked ... Clutch Cable change?    |    3 hours ago Richard asked ... Mountfield SP414 mower, revs too high?    |    Don asked ... Find the charger or how to convert the battery?    |    Tanzania asked ... How can i mend my sanyo fwbp505f q?    |    Mark Goodwin asked ... Mount field 725m ride on mower?    |    Click here to ask your question

ravenheat csi85t combi boiler cuts off after a few seconds?

my ravenheat csi85t cuts off after afew seconds and there is a very loud boiling and air bubbling sound air release valve seems to be working but water has been forced out of the pipe at the air valve cant understand it any ideas
william, February 2009
My csi 120 did the same!
see if the pressure clock goes way up when you try firing up the boiler.
If it does, then check the pump is running.

The plug connecting to the pump had become loose,it caused a rapid pressure rise when it fired up, and tripped the over pressure cutout.

Colin, February 2009
poss a massive air lock or the pumps not running

jim, February 2009