2 hours ago Ariana Orellana asked ... Code?    |    Lynnie asked ... BT Studio 4500 cordless telephone?    |    David Dawes asked ... How to recoil the starter spring - Champion R484TR?    |    peter high asked ... How can I set time on my Neff oven?    |    Michael asked ... Mountfield empress drive belt?    |    Click here to ask your question

halstead ace high over pressurising?

I have a 5 year old Halstead Ace High boiler recently when the central heating is running the pressure has been rising from 1 bar to 3 bar within the first hour of the central heating coming on. The pressure is releasing through the prv like it should do, i have no visible leaks and have checked the expansion vessell which is charged to 1 bar. it seems that the boiler is only happy running from a static 0.25 bar which isn't right, a mate of mine seems to think i need a new expansion vessell but when the pressure is released from the expansion vessell through the charging valve there is no evidence of water contamination.has anybody got any ideas, thanks
dave, February 2009
link Click here to see other fixes for Halstead Ace High.