3 hours ago Sandy asked ... Replace vertical gear on Singer Fashion Mate 252?    |    Blaablaa asked ... How can I fix?    |    pete asked ... Flymo 330 turboglide?    |    keith asked ... Fuseboard( s) location of renault trafic t1100 1993?    |    Janet asked ... Neff B1641 door not closing at top?    |    Click here to ask your question

Ferrpli F30 over pressure?

My Ferroli F30 works well except when the heating is on the pressure in the system goes over 3.5 bar and the P.R.V dumps the excess as it is supposed to do. The starting pressure is 1 bar. I understand from the manuel the normal running pressure is 1.5 to 2 bar. When the system has cooled down the pressure is 1/2 a bar. All the rads are getting hot. Any help would be appreciated.
Jeff Bridgend, May 2009
Problem solved,
The Shrader valve on the expansion vessel had failed.
All the air pressure had been lost. I replaced the valve and repressurised the tank. It all works perfectly now. Tulas you were not far off the mark.
Thanks

Jeff Bridgend, May 2009
expansion vessel goosed or pipework 2 it is blocked

tulsa mclean, May 2009
link Click here to see other fixes for Ferroli F30.