Sandy asked ... Replace vertical gear on Singer Fashion Mate 252?    |    Blaablaa asked ... How can I fix?    |    pete asked ... Flymo 330 turboglide?    |    keith asked ... Fuseboard( s) location of renault trafic t1100 1993?    |    Janet asked ... Neff B1641 door not closing at top?    |    Click here to ask your question

worcester 24i combi , overflow leaking , pressure to 3 bar , ?

just replaced water feed and another part which started to leak after i had blown the system of water, i think this was the ball valve,this is the 2nd time in a month , whats else could it be ?, thanks
northener, May 2009
Overflow will run at 3-00 Bar pressure, this should be reduced to 1-00 Bar, make sure the filling loop is completely turned off afterwards, you could have a problem with the expansion vessel, if the pressure rises and falls significantly

www.elanar.co.uk, May 2009