Sandy asked ... Replace vertical gear on Singer Fashion Mate 252?    |    Blaablaa asked ... How can I fix?    |    pete asked ... Flymo 330 turboglide?    |    keith asked ... Fuseboard( s) location of renault trafic t1100 1993?    |    Janet asked ... Neff B1641 door not closing at top?    |    Click here to ask your question

potterton performa 24 preasure riseing?

the pressure keeps going up every time the boiler fires up. i reduce the pressure back to 1 bar but it climbes every time . The filling loop is not connected .
chris, October 2009
flat expansion vessel, needs re-charging to just under 1 bar with a footpump-best to get experienced engineer to carry out this

STUBOW, October 2009