Don asked ... Find the charger or how to convert the battery?    |    Tanzania asked ... How can i mend my sanyo fwbp505f q?    |    Mark Goodwin asked ... Mount field 725m ride on mower?    |    Joan Sorrentino asked ... Barcalounger issue?    |    David asked ... Not starting until I bang door closed?    |    Click here to ask your question

potterton profile 50e burner goes out?

Having switched on all appears ok.fan, pilot, main burner, all start as usual. Then after a short time main burner goes off.Pilot & fan remain on, but main burner remains off.Heating pipes only barely detectable warm. pump running ok. Boiler is on gravity HW system & set for it.
Harold B, November 2009
check overheat stat or thermistor with multimeter or replace them (both pretty cheap) this may be why boiler goes off after a short time. if not these you may have a faulty gas valve, bit more expensive.

jason, November 2009