Katie Bond asked ... Fixing auto threader on Baby Lock Enlighten Overlocker?    |    Chris. asked ... Miele W800 novotronic washing machine?    |    Larry asked ... How to stop my steam iron from leaking. Model dw2463 Rowenta?    |    HT asked ... Radio code Philips 22RC200/35?    |    Roberta asked ... DW5080?    |    Click here to ask your question

baxi solo plf not firing for c/h but is for h/w any ideas???

i have a baxi solo plf and the boiler is not firing up when i turn on c/h system however the boiler is turning on when i turn on the h/w system any help would be appriciated ???
aidenf, January 2010
Could be the 3 port valve, not changing over to c/h or the electrical contacts are dirty. Stand by the 3 port valve & get someone else to switch c/h on. Listen for the motorised 3 port valve to change over (sometimes it has a lever on it that can be viewed moving from h/w to c/h). If the valve changes from h/w to c/h but boiler does not start then the auxilliary contacts on the 3 port valve are faulty (not passing 240v to boiler). 3 port valves cost about £35 from screwfix - next day delivery.

John L, January 2010
link Click here to see other fixes for Baxi.