John asked ... Scantronix 9450 box stuck shut?    |    Pekaye asked ... Clutch Cable change?    |    Richard asked ... Mountfield SP414 mower, revs too high?    |    Don asked ... Find the charger or how to convert the battery?    |    Tanzania asked ... How can i mend my sanyo fwbp505f q?    |    Click here to ask your question

Low water pressure on glow worm 30ci?

Why won't the water pressure increase when the filling device tap is opened on my glow worm 30ci? Both filters have been cleaned and refitted. System was previously running perfectly.
Steve, April 2010
Thanks Boilerman, but pressure coming into system seems fine, it's just that nothing happens when I open the filling device. Also the system is sound, in that there are no leaks. I'm confused!!

Steve, April 2010
Is your water main at 2 bar or above? This is an exerpt from the boiler installation manual.

• If the boiler loses water: the pressure will be indicated (a)
and the boiler ON indicator (b) will flash red indicating a fault.
Fill the system by the filling device (c) at the bottom of the boiler
until the pressure gauge reads 1.0 bar.
A mains inlet pressure of 2.0 bar is required to reach a fill
pressure of 1.0 bar.

TheBoilerMan, April 2010