3 hours ago Sandy asked ... Replace vertical gear on Singer Fashion Mate 252?    |    Blaablaa asked ... How can I fix?    |    pete asked ... Flymo 330 turboglide?    |    keith asked ... Fuseboard( s) location of renault trafic t1100 1993?    |    Janet asked ... Neff B1641 door not closing at top?    |    Click here to ask your question

Worcester Bosch Greenstar 15Ri fault?

My boiler clicks like mad then goes into fault mode, light off long - light on short!
My engineer is at a loss he has tried/changed everything but he has noticed when it goes into fault mode a spurious 40v appears on the switched live at the boiler?
Mr E, May 2010
my green burner light is not coming on everything else is lit but of course without the burner no start up

stephen, March 2011
capacitor is required on switch live and neutral at boiler

boiler man, May 2010
40v voltage could mean that it may not be the boiler, but a motorised valve, or a jammed/defective gas valve. Your Engineer should have placed a call to Worcester technical dept, they will run through the full test procedure with him over the phone.

Dave, May 2010
link Click here to see other fixes for Bosch Greenstar.