4 hours ago Pekaye asked ... Clutch Cable change?    |    4 hours ago Richard asked ... Mountfield SP414 mower, revs too high?    |    Don asked ... Find the charger or how to convert the battery?    |    Tanzania asked ... How can i mend my sanyo fwbp505f q?    |    Mark Goodwin asked ... Mount field 725m ride on mower?    |    Click here to ask your question

ravenheat boiler problem?

got a ravenheat csi 120 and the pressure keeps rising until pressure release kicks in. the filling loop is disconnected and when i turn the cold water supply off it stops filling. i`m assuming the divertor valve sticking. took it out and cleaned and checked it but appears ok. anyone any ideas
desperado, June 2010
Flat plate exchanger leaking cold feed into heating circuit system over pressurising to water main pressure and hence lifting safety valve, diverter valve only diverts hot boiler water either to C.H system or to D.H.W via the flat plate type exchanger.

Guytawe, June 2010