Freya asked ... Frister & Rossman Cub7 Sewing Machine?    |    katlego asked ... Rev count on my 1982?    |    andrew asked ... "SECURE" on a yellow backround, and I cant ge?    |    Melodie asked ... How do I remove and change the basket? Duratech Identity Gu?    |    Kathy asked ... Samsung ER-4915?    |    Click here to ask your question

how do i fix a filling loop on my greenstar 24i junior?

i think my external filling loop as come off.i have a flexible hose which i belive was connected to the cold tap but i dont know where to connect too from there.can someone please help me
TERESA BAGGETT, July 2010
Below the boiler (I'm assuming here), there will be two silver valves attached to two pipes, one should be on the far right of the pipes that come down (a 22mm or 3/4" pipe), the next valve should be on the pipe next to it (15mm or1/2" pipe next to it), the flexible loop connects to those two valves.

There are different types of valves (dependant on make), some are quarter turn screw valves that turn with a screwdriver, others are plastic finger type turn valves.
Again dependant on the make, either only one of the valves will need turning to fill the system, or sometimes both valves need to be opened.

When filling, watch the pressure guage on the boiler, fill the boiler (when cold) to 1-1.5 bar, then turn the valve(s) off.

Carefree, July 2010