3 hours ago Pekaye asked ... Clutch Cable change?    |    4 hours ago Richard asked ... Mountfield SP414 mower, revs too high?    |    Don asked ... Find the charger or how to convert the battery?    |    Tanzania asked ... How can i mend my sanyo fwbp505f q?    |    Mark Goodwin asked ... Mount field 725m ride on mower?    |    Click here to ask your question

Ravenheat boiler not staying lite?

I have a Ravenheat CSI Primary A condensing boiler it goes through the start proccess main burner comes in for 5-6 seconds then the boiler switchs off I have replaced the overheat stat and the airflow switch but the boiler is still the same.
Jeff Hilditch, July 2010
Flame rectification.

Check for decent earth connection to the boiler and correct polarity between L & N.
Check lead for ignition/rectification in good condition and not 'trapped'.
Also check the condense waste system is clear.

Carefree, July 2010
link Click here to see other fixes for Ravenheat CSI Primary A.