Sandy asked ... Replace vertical gear on Singer Fashion Mate 252?    |    Blaablaa asked ... How can I fix?    |    pete asked ... Flymo 330 turboglide?    |    keith asked ... Fuseboard( s) location of renault trafic t1100 1993?    |    Janet asked ... Neff B1641 door not closing at top?    |    Click here to ask your question

Fluctuating Pressure on Baxi 105E?

I recently had the expansion vessel replaced in my baxi 105e. (due to high pressure when heating on) . Now the pressure sits at around 1 bar when cold, and goes down just below 0.5 when firing up then up to 2 bar when full heating on. However when I have the boiler set to hot water on demand only, when I run hot taps from cold, the pressure drops to 0.5 bar and the water pipes/boiler makes a funny noise. what is going on? Can anyone help?? why would the pressure fluctuate so wildly in operation? We live in a large 3-bed tenement flat... Thanks for any advice.
Lucy Glasgow, November 2010
expansion vessel not pressurised you ccan do it with a bicycle pump and pressure gauge set it to 3 bar

davy, November 2010