46 mins ago Sandy asked ... Replace vertical gear on Singer Fashion Mate 252?    |    Blaablaa asked ... How can I fix?    |    pete asked ... Flymo 330 turboglide?    |    keith asked ... Fuseboard( s) location of renault trafic t1100 1993?    |    Janet asked ... Neff B1641 door not closing at top?    |    Click here to ask your question

the boiler dose not cut in automatically?

potterton netaheat profile 50e boiler. my boiler dose not cut in automatically when the tempreture drops,do you know where i can purchase a manual. the boiler was already in place when i purchased the house.the only way i can get the boiler working, is by pressing a button underneath the boiler.then it only works for about an hour-then switches off.
mr dave gilbert, November 2010
To all those wanting a copy of the Potterton netaheat boiler manual, your wait is nearly over: http://driverrob.wordpress.com/2011/01/29/potterton-netaheat-boiler-manual-get-it-here/

Rob, January 2011
The button you are pressing sounds like the overheat thermostat reset button (hole underneath boiler cover towards the right hand side). The boiler could be overheating for a number of reasons:

Main thermostat allowing overheat:

Pump overrun thermostat shutting down too early (therefore faulty):

Pump not operating/running too slowly:

Pump live not wired into boiler (installation fault):

Carefree, November 2010