Don asked ... Find the charger or how to convert the battery?    |    Tanzania asked ... How can i mend my sanyo fwbp505f q?    |    Mark Goodwin asked ... Mount field 725m ride on mower?    |    Joan Sorrentino asked ... Barcalounger issue?    |    David asked ... Not starting until I bang door closed?    |    Click here to ask your question

E133 error code?

Hi

I have a combi boiler Promax Combi HE Plus A, i keep getting error code E133 which is a gas supply fault, due to the extremely cold weather lately and from what i could find out on google, i think it may be condensate drain system pipe that is frozen. As heating engineers cannot get to me immediatley (and for the sake of my 9 year old) I have scoured the internet to find out where this pipe is located (I,m not blonde) and apparently easiest way to thaw out is boiling water being poured over the pipe... thing is and excuse me if this seems really obvious to you all but
am I supposed to do that on the pipe inside or outside.. if it outside its going to be impossible as I live in a second floor flat.. please advise, thanks.. Kathy
kathy, December 2010
it is the white pipe under the boiler and it will go outside you can cut it outside as a temp measure and it will drain cut it at the top

Paul, December 2010