Don asked ... Find the charger or how to convert the battery?    |    Tanzania asked ... How can i mend my sanyo fwbp505f q?    |    Mark Goodwin asked ... Mount field 725m ride on mower?    |    Joan Sorrentino asked ... Barcalounger issue?    |    David asked ... Not starting until I bang door closed?    |    Click here to ask your question

Why would overflow valve be spilling water on floor?

The overflow valve on my furnace is spilling large amounts of water on basement floor. What is the reason for this. Could the problem lie in the Aquastat Relay? This is not about an oil filled radiator, it is an oil fired furnace (Becket burner).
Marie, December 2010
if boiler pressure gauge reaches 30 psi it is designed to relieve pressure.most common problem,expansion tank bladder has ruptured or older style tank needs to be drained of water and then valve needs to be opened back up. also feed valve could be allowing to much pressure in.

gilles, December 2010