Pekaye asked ... Clutch Cable change?    |    Richard asked ... Mountfield SP414 mower, revs too high?    |    Don asked ... Find the charger or how to convert the battery?    |    Tanzania asked ... How can i mend my sanyo fwbp505f q?    |    Mark Goodwin asked ... Mount field 725m ride on mower?    |    Click here to ask your question

low pressure?

Glow-worm CXI30 loosing pressure 2bar to 0 in 8hours no obvious leaks on circuits or boiler, same with heating circuit shut down at boiler.
robbo, December 2010
I have a glow worm compact 100e and has been doing the same problem over the last few weeks. The water tho has been dripping out of the PRV (pressure relief valve) and loosing pressure when the heating is on and goes down to about 2bar then stops dripping, then when its stone cold again the pressure is about 5bar. It turns out that the expansion vessel needs re-pressurising. maybe the same with yours?
Billybob.

Billybob, January 2011