Don asked ... Find the charger or how to convert the battery?    |    Tanzania asked ... How can i mend my sanyo fwbp505f q?    |    Mark Goodwin asked ... Mount field 725m ride on mower?    |    Joan Sorrentino asked ... Barcalounger issue?    |    David asked ... Not starting until I bang door closed?    |    Click here to ask your question

ravenheat csi85BT?

my boiler fires up for about 20 seconds then goes out and lockout light comes on, reset and just does the same over again.if i operate the air pressure switch manually and hold the air tube so the switch stays made the boiler works.its had new air pressure switch,new fan and i have checked the casing and flue for any holes or blockages where i could lose the air pressure found none, any ideas please i have had enough of it
dave derbyshire, January 2011
have done that brian still not working just want to hit it with a big hammer, hate ravenheat any other ideas please

dave derbyshire, January 2011
clean venturi tube on flue one of the rubber tubes goes to a spigot on the flue just above the fan remove and thoroughly clean the spigot hopefully this will cure the problem

brian, January 2011