Katie Bond asked ... Fixing auto threader on Baby Lock Enlighten Overlocker?    |    Chris. asked ... Miele W800 novotronic washing machine?    |    Larry asked ... How to stop my steam iron from leaking. Model dw2463 Rowenta?    |    HT asked ... Radio code Philips 22RC200/35?    |    Roberta asked ... DW5080?    |    Click here to ask your question

bosch zwb7-32 rd532 condensing boiler?

the pressure guage on the boiler keeps going to 3 & water keeps dripping out of the relief valve.I have drained the system to take it down to 1 bar, but when the heating comes back on it goes back up to 3 bar. Does anyone out there know how to fix this problem. Thanks Kev
Kev, March 2011
Further thoughts. Is expansion vessel seal blown so no space behind diaphragm for expansion, or simplest possibility, is the fill permanently connected to mains, and the shut off valve is letting by. My daughter has this boiler, and with fill pipe disconnected from the valve, the valve lets by so needs a cap.

Gonky, March 2011
Could be the expansion vessel needs to be larger

Gonky, March 2011