Don asked ... Find the charger or how to convert the battery?    |    Tanzania asked ... How can i mend my sanyo fwbp505f q?    |    Mark Goodwin asked ... Mount field 725m ride on mower?    |    Joan Sorrentino asked ... Barcalounger issue?    |    David asked ... Not starting until I bang door closed?    |    Click here to ask your question

how can i fix my Sime Friendly Format 100E Boiler?

When the hot water is drawn off the boiler fires up heats the water the boiler then cuts in & out so the shower goes hot & cold i have replaced the DHW heat exchanger & the diaphagm in the diverter valve can anybody help me
Alan, March 2011
check your shower is passing more than the minimum flow rate for boiler 9-10 ltrs per min or above should be ok after that it may be a thermostat/thermistor problem

brian, March 2011