2 hours ago John asked ... Scantronix 9450 box stuck shut?    |    Pekaye asked ... Clutch Cable change?    |    Richard asked ... Mountfield SP414 mower, revs too high?    |    Don asked ... Find the charger or how to convert the battery?    |    Tanzania asked ... How can i mend my sanyo fwbp505f q?    |    Click here to ask your question

Avanta plus 24?

when i turn on my heating the boiler goes through its cycle, then the boiler fires up then after 6 seconds locks out coming up with the code E5. to get hot water you have to run the tap untill again the boiler goes through its cycle and when it fires the hot water will come through, as soon as you turn off the tap it locks out again with the code E5 . . .any ideas folk.
leon reynolds, December 2011
Not specific to you, as I do not know the model.
General things to check. From what you say, you get hot water, but when heating is called for fault.
check pressure, usually about 1 bar when cold. try turning the heating control to a lower setting, it could be over heat sensor, do you have thermostatic radiator valves, can you hear the pump running, If no pump, it would overheat very quick and close down, open the unit up, on end of pump, a big plastic screw, if you remove that, some water will come out, but you can put a screwdriver in to turn the pump to check if free. if stuck new pump. hope this helps a bit

SD, December 2011