Don asked ... Find the charger or how to convert the battery?    |    Tanzania asked ... How can i mend my sanyo fwbp505f q?    |    Mark Goodwin asked ... Mount field 725m ride on mower?    |    Joan Sorrentino asked ... Barcalounger issue?    |    David asked ... Not starting until I bang door closed?    |    Click here to ask your question

Worcester oil boiler; hot water on CH off, but CH keeps working?

I have a Worcester Heatslave oil boiler. the HW is on constant but when it kicks in to warm up the water, the CH also kicks in despite the CH being in timer mode and not due on
Jason B, January 2012
i'm an oftec engineer...lots of experience with heatslaves.
your boilers mid position motorised valve is faulty. replace the actuator head.